Complete guide to fire alarm permit requirements in Plano, Texas. SFMO licensing required. 2024 IFC adopted August 1. Fire Marshal plan review process.
# Fire Alarm Permit Requirements in Plano, Texas
**Quick Answer:** Fire alarm installations in Plano, Texas require permits from the Plano Fire Marshal's Office. Contractors must hold a Texas State Fire Marshal Office (SFMO) fire alarm license. Plano adopted 2024 International Fire Code effective August 1, 2024.
## Do I Need a Permit for Fire Alarm Work in Plano?
Yes. Plano requires fire alarm permits for:
- **New fire alarm installations** - All occupancies
- **System modifications** - Adding or relocating devices
- **Panel replacements** - Including upgrades
- **Annunciator installations** - Remote displays
- **Integration work** - Elevator recall, HVAC, door release
- **Annual testing** - Certification documentation required
## 2024 Fire Code Adoption
Plano adopted the **2024 International Fire Code (IFC)** effective August 1, 2024. Key requirements:
### NFPA 72 Compliance
The 2024 IFC references NFPA 72 for fire alarm design and installation standards:
- Device spacing requirements
- Audibility and intelligibility requirements
- Secondary power requirements
- Documentation requirements
### Voice Evacuation
Required in:
- High-rise buildings
- Assembly occupancies over 300
- Covered malls
- Healthcare facilities
## Permit Application Process
### Step 1: Fire Marshal Plan Review
Submit plans to Fire Prevention for review before construction permit:
**Required Submittals:**
- Floor plans at 1/8" minimum scale
- Device locations with coverage calculations
- Riser diagram with device counts
- Equipment specifications
- Battery calculations
- Voltage drop calculations
- Sequence of operations
- **SFMO license documentation**
### Step 2: Plan Review Period
- **Standard review:** 10-15 business days
- **Complex projects:** May require additional time
- **Resubmittals:** 5-10 business days
### Step 3: Obtain Construction Permit
After fire alarm approval:
- Apply for electrical/building permit
- Reference approved fire plans
- Pay permit fees
### Step 4: Inspections
- **Rough-in inspection** - Before wall/ceiling closure
- **Final inspection** - Complete system test
## Texas SFMO Licensing
### Required Licenses
All fire alarm work requires SFMO licensing:
- **Fire Alarm Superintendent (FAP)** - Project oversight
- **Fire Alarm Technician (FAT)** - Installation work
- **Alarm Planning Superintendent (APS)** - Plan signatures
### License Verification
Plano verifies SFMO licensing during plan review. Maintain current license status.
### NICET Certification
While not legally required, many projects specify:
- NICET Level II minimum for technicians
- NICET Level III for project managers
- NICET Level IV for design responsibility
## Inspection Process
### Rough-In Inspection
Schedule before closing walls:
- Device mounting heights verified
- Conduit and pathway inspection
- Fire stopping at penetrations
- Wire supervision confirmation
### Final Inspection
Complete acceptance testing:
- **100% functional test** of all devices
- **Audibility measurements** documented
- **Intelligibility testing** (if voice)
- **Battery load test** with calculations verified
- **Central station verification**
- **Record of completion** submission
## Permit Fees
| Service | Fee |
|---------|-----|
| Plan Review | Based on project size |
| Construction Permit | Based on valuation |
| Re-inspection | Additional fee |
| After-hours | Premium rates |
## False Alarm Impact
With ~12,000 false alarms annually in Plano, fire prevention takes this seriously:
### Prevention Measures
- Proper detector selection for environment
- Construction mode during renovation
- Training for building occupants
- Regular maintenance schedule
### Documentation
- Maintain service records
- Document false alarm causes
- Provide correction evidence
- Train monitoring company contacts
## Pro Tips for Plano Fire Alarm Projects
1. **Use 2024 IFC** - Effective August 1, 2024
2. **Submit Complete Packages** - Missing items delay review
3. **Include APS Signature** - Required on all plans
4. **Plan for Voice Requirements** - More occupancies require it
## Timeline
| Phase | Duration |
|-------|----------|
| Plan Review | 10-15 business days |
| Permit Issuance | 1-2 days after approval |
| Rough-In Inspection | 24-48 hour scheduling |
| Final Inspection | 24-48 hour scheduling |
## Contact Information
**Plano Fire Prevention**
- Phone: (972) 941-7143
- Address: 1520 K Avenue, Suite 170, Plano, TX 75074
**Plano Development Services**
- Permit Portal: www.plano.gov/permits
- Phone: (972) 941-7151
**Texas State Fire Marshal Office**
- Website: www.tdi.texas.gov/fire
- Phone: (512) 676-6000
## Stay Ahead of Permit Activity
Want to know when fire alarm projects hit permits in Plano before they reach bid boards?
[LVN Signal](https://www.lowvoltagenation.com/signal) monitors permit activity across Texas and alerts you to opportunities the moment they are filed.
→ [Explore Signal](https://www.lowvoltagenation.com/signal)
---
*Last verified: January 2026. Requirements may change. Contact Plano Fire Prevention for current requirements.*